イートン モーラー FAZ-C4/3 小型サーキットブレーカー

$110.00

  • 部品番号 FAZ-C4/3
  • メーカーイートン・モーラー
  • 空室状況 Out of Stock
  • 推定リードタイム: 1-2week
  • コンディション 新品
  • 保証:12ヶ月

製品データシート

説明

Information

Eaton Moeller series xEffect – FAZ MCB. FAZ, 3-pole, tripping characteristic: C, rated current In: 4 A

Technical Specifications

Product Length/Depth

80 mm

Product Height

75.5 mm

Product Width

54 mm

Product Weight

0.338 kg

Compliances

UL CSA09 (with supplementary protector only)

RoHS conform

Certifications

CSA (Class No. 3215-30)

UL 1077

UL (File No. E177451)

North America (UL recognized, CSA certified)

IEC/EN 60947-2

IEC/EN 60898

CSA-C22.2 No. 235

UL (Category Control Number QVNU2, QVNU8)

CSA (File No. 204453)

CE marking

EN45545-2

IEC 61373

Rated operational current for specified heat dissipation (In)

4 A

10.11 Short-circuit rating

Is the panel builder’s responsibility. The specifications for the switchgear must be observed.

Voltage rating (IEC/EN 60898-1)

415 VAC

10.4 Clearances and creepage distances

Meets the product standard’s requirements.

Rated short-circuit breaking capacity (EN 60898) at 230 V

10 kA

10.12 Electromagnetic compatibility

Is the panel builder’s responsibility. The specifications for the switchgear must be observed.

Mounting Method

Top-hat rail IEC/EN 60715

Current limiting class

3

Rated short-circuit breaking capacity (EN 60898) at 400 V

10 kA

Amperage Rating

4 A

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

Terminal capacity of screw terminals for main cable

10 mm² (2x)

Frequency rating – max

60 Hz

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard’s requirements.

10.8 Connections for external conductors

Is the panel builder’s responsibility.

Rated short-circuit breaking capacity (IEC 60947-2) at 400 V

15 kA

Number of poles (total)

3

Terminal protection

Finger and hand touch safe, DGUV VS3, EN 50274

Rated short-circuit breaking capacity (IEC 60947-2) at 230 V

15 kA

Special features

Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity

Ambient operating temperature – max

75 °C

Heat dissipation per pole, current-dependent

0 W

Built-in depth

70.5 mm

Rated switching capacity (IEC/EN 60898-1)

10 kA

Features

Additional equipment possible

Lifespan, electrical

10000 operations

Rated switching capacity (IEC/EN 60947-2) at max voltage rating

10 kA

Connectable conductor cross section (solid-core) – min

1 mm²

10.9.3 Impulse withstand voltage

Is the panel builder’s responsibility.

Number of poles

Three-pole

Ambient operating temperature – min

-25 °C

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

Selectivity class

3

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

Terminal capacity (control cable)

25 mm² (1x)

Used with

FAZ

Miniature circuit breaker

Mounting position

As required

Equipment heat dissipation, current-dependent

4.4 W

Tripping characteristic

C

Frequency rating – min

50 Hz

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder’s responsibility.

Static heat dissipation, non-current-dependent

0 W

Application

Branch circuits, not as BCPD

Switchgear for industrial and advanced commercial applications

xEffect – Switchgear for industrial and advanced commercial applications

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

Voltage type

AC

Number of poles (protected)

3

Frame

45 mm

Terminals (top and bottom)

Twin-purpose terminals

Heat dissipation capacity

0 W

Release characteristic

C

Width in number of modular spacings

3

Busbar material thickness

0.8 mm – 2 mm

Power loss

4.5 W

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard’s requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard’s requirements.

Enclosure width

80 mm

Voltage rating

240 V AC / 415 V AC

10.9.2 Power-frequency electric strength

Is the panel builder’s responsibility.

Connectable conductor cross section (solid-core) – max

25 mm²

Degree of protection

IP20 (IEC)

UL/CSA Type: –

IP40 (when fitted)

IP20

Overvoltage category

III

Pollution degree

2

10.7 Internal electrical circuits and connections

Is the panel builder’s responsibility.

Connectable conductor cross section (multi-wired) – min

1 mm²

Rated impulse withstand voltage (Uimp)

4 kV

Operational voltage (IEC/EN 60947-2) – max

440 VAC

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Voltage rating at DC

60 V DC (per pole)

Admissible back-up fuse – max

125 A gL/gG

Voltage rating (UL)

480Y/277 V

Rated switching capacity (IEC/EN 60947-2)

15 kA

Voltage rating (UL CSA 13)

480 Y/277 V AC

Connectable conductor cross section (multi-wired) – max

25 mm²

Mounting width per pole

17.5 mm

Type

FAZ

Miniature circuit breaker

10.2.2 Corrosion resistance

Meets the product standard’s requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard’s requirements.

10.2.7 Inscriptions

Meets the product standard’s requirements.

Operational switching capacity

7.5 kA

Breaking capacity

10 kA (UL1077)

Direction of incoming supply

As required

Rated operational voltage (Ue) – max

400 V

Rated service short-circuit breaking capacity (IEC/EN 60898-1)

7.5 kA

Mounting width

17.5 mm

Rated service short-circuit breaking capacity (IEC/EN 60947-2)

7.5 kA

Rated insulation voltage (Ui)

440 V

FAZ-C4-3

追加情報
重さ 1 kg
サイズ 20 × 15 × 15 cm
レビュー (0)

レビュー

レビューはまだありません。

“Eaton Moeller FAZ-C4/3 Miniature Circuit Breaker” の口コミを投稿します
配送

1.配達細部:私達は支払のレシートに1-5仕事日以内のすべての項目を、私達の目的である出荷する: 私達ができるとすぐそれを出荷しなさい。
2.We はそのような運送会社を使用して配達を世界的にのように提供します: DHL、FEDEX、UPS、米国への、必要性 3-4 仕事日、他の国への、必要性 4-8 仕事日普通。しかし時々 int'l 配達は非常に急使会社およびローカル習慣/義務によって決まります。
3.通常配達更新システムに遅れがある; 数日の時間のあなたの項目を追跡することを考慮するかもしれない。
4.All 追跡番号はあなたの paypal の電子メールに小包の後で時間制限の後でそれを受け取らなかったら、ちょうど私達に連絡すること自由に感じられます送られます。
5.輸入関税および税金は項目価格か発送料に含まれていません。これらの充満はバイヤー責任である。