Eaton 277011 DILM17-10(220V50/60HZ) DILM Contactor, 220 V ac, 230 V dc Coil, 3-Pole, 3.5 kW, 1NC
$95.00
- Numero di parte: 277011 DILM17-10(220V50/60HZ)
- Produttore:Eaton
- Disponibilità: in stock
- Tempi di consegna stimati: Solitamente viene spedito in 1-5 giorni lavorativi
- Condizioni: Nuovo di zecca
- Garanzia :12 mesi
General Specifications
Nome del prodotto | Eaton Moeller® series DILM contactor |
Numero di catalogo | 277011 |
EAN | 4015082770112 |
Lunghezza/profondità del prodotto | 97 mm |
Altezza del prodotto | 85 mm |
Larghezza del prodotto | 45 mm |
Peso del prodotto | 0.428 kg |
Certificazioni | UL File No.: E29096 CSA Class No.: 2411-03, 3211-04 UL CSA VDE 0660 CSA File No.: 012528 IEC/EN 60947-4-1 CSA-C22.2 No. 60947-4-1-14 CE IEC/EN 60947 UL 60947-4-1 UL Category Control No.: NLDX |
Catalog Notes | Contacts according to EN 50012 |
Codice modello | DILM17-10(220V50/60HZ) |
Product specifications
Electrical connection type for auxiliary- and control-current circuit | Collegamento a vite |
Numero di pali | A tre poli |
Tensione nominale | 220 V |
10.10 Aumento della temperatura | Il costruttore del pannello è responsabile del calcolo dell'aumento di temperatura. Eaton fornirà i dati di dissipazione del calore per i dispositivi. |
10.11 Valutazione del cortocircuito | È responsabilità del costruttore del quadro. È necessario rispettare le specifiche del quadro. |
10.12 Compatibilità elettromagnetica | È responsabilità del costruttore del quadro. È necessario rispettare le specifiche del quadro. |
10.13 Funzione meccanica | Il dispositivo soddisfa i requisiti, a condizione che vengano rispettate le informazioni contenute nel foglietto illustrativo (IL). |
10.2.2 Resistenza alla corrosione | Soddisfa i requisiti dello standard di prodotto. |
10.2.3.1 Verifica della stabilità termica degli involucri | Soddisfa i requisiti dello standard di prodotto. |
10.2.3.2 Verifica della resistenza dei materiali isolanti al calore normale | Soddisfa i requisiti dello standard di prodotto. |
10.2.3.3 Resistenza del materassino isolante a calore/incendio anomalo per effetto dell'elettricità interna | Soddisfa i requisiti dello standard di prodotto. |
10.2.4 Resistenza ai raggi ultravioletti (UV) | Soddisfa i requisiti dello standard di prodotto. |
10.2.5 Sollevamento | Non si applica, poiché è necessario valutare l'intero quadro elettrico. |
10.2.6 Impatto meccanico | Non si applica, poiché è necessario valutare l'intero quadro elettrico. |
10.2.7 Iscrizioni | Soddisfa i requisiti dello standard di prodotto. |
10.3 Grado di protezione degli assiemi | Non si applica, poiché è necessario valutare l'intero quadro elettrico. |
10.4 Distanze e distanze di dispersione | Soddisfa i requisiti dello standard di prodotto. |
10.5 Protezione contro le scosse elettriche | Non si applica, poiché è necessario valutare l'intero quadro elettrico. |
10.6 Inclusione di dispositivi e componenti di commutazione | Non si applica, poiché è necessario valutare l'intero quadro elettrico. |
10.7 Circuiti elettrici interni e collegamenti | È responsabilità del costruttore del pannello. |
10.8 Collegamenti per conduttori esterni | È responsabilità del costruttore del pannello. |
10.9.2 Forza elettrica a frequenza di alimentazione | È responsabilità del costruttore del pannello. |
10.9.3 Tensione di tenuta all'impulso | È responsabilità del costruttore del pannello. |
10.9.4 Prova di involucri in materiale isolante | È responsabilità del costruttore del pannello. |
Frequency rating | 50-60 Hz |
Operating frequency | 5000 mechanical Operations/h (AC operated) |
Grado di inquinamento | 3 |
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Connection to SmartWire-DT | No |
Tensione nominale di resistenza agli impulsi (Uimp) | 8000 V AC |
Utilization category | AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
Connessione | Terminali a vite |
Frame size | FS2 |
Temperatura ambiente di funzionamento - max | 60 °C |
Temperatura ambiente di funzionamento - min | -25 °C |
Ambient operating temperature (enclosed) – max | 40 °C |
Ambient operating temperature (enclosed) – min | 25 °C |
Ambient storage temperature – max | 80 °C |
Ambient storage temperature – min | 40 °C |
Assigned motor power at 115/120 V, 60 Hz, 1-phase | 2 HP |
Assigned motor power at 200/208 V, 60 Hz, 3-phase | 5 HP |
Assigned motor power at 230/240 V, 60 Hz, 1-phase | 3 HP |
Assigned motor power at 230/240 V, 60 Hz, 3-phase | 5 HP |
Assigned motor power at 460/480 V, 60 Hz, 3-phase | 10 HP |
Assigned motor power at 575/600 V, 60 Hz, 3-phase | 15 HP |
Conventional thermal current Ith (1-pole, enclosed) | 80 A |
Conventional thermal current Ith (3-pole, enclosed) | 32 A |
Conventional thermal current Ith at 55°C (3-pole, open) | 37 A |
Conventional thermal current Ith of main contacts (1-pole, open) | 88 A |
Equipment heat dissipation, current-dependent Pvid | 2.1 W |
Heat dissipation capacity Pdiss | 0 W |
Heat dissipation per pole, current-dependent Pvid | 0.7 W |
Applicazione | Contactors for Motors |
Product category | Contactors |
Protezione | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
Arcing time | 10 ms |
Electrical connection type of main circuit | Collegamento a vite |
Screwdriver size | 2, Terminal screw, Pozidriv screwdriver 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver |
Tipo di tensione | AC |
Grado di protezione | IP00 |
Number of auxiliary contacts (normally closed contacts) | 0 |
Number of auxiliary contacts (normally open contacts) | 1 |
Number of contacts (normally closed) as main contact | 0 |
Number of contacts (normally open contacts) | 1 |
Number of main contacts (normally open contact) | 3 |
Rated breaking capacity at 220/230 V | 170 A |
Rated breaking capacity at 380/400 V | 170 A |
Rated breaking capacity at 500 V | 170 A |
Rated breaking capacity at 660/690 V | 120 A |
Rated control supply voltage (Us) at AC, 50 Hz – max | 220 V |
Rated control supply voltage (Us) at AC, 50 Hz – min | 220 V |
Rated control supply voltage (Us) at AC, 60 Hz – max | 220 V |
Rated control supply voltage (Us) at AC, 60 Hz – min | 220 V |
Contact configuration | 1 NO |
Drop-out voltage | AC operated: 0.6 – 0.3 x UC, AC operated |
Categoria di sovratensione | III |
Duty factor | 100 % |
Emitted interference | According to EN 60947-1 |
Interference immunity | According to EN 60947-1 |
Lifespan, mechanical | 10,000,000 Operations (AC operated) 7,000,000 Operations (Coil 50/60 Hz) |
Pick-up voltage | 0.8 – 1.1 V AC x Uc |
Power consumption, pick-up, 50 Hz | 58 VA, Dual-frequency coil in a cold state and 1.0 x Us 62 VA, Dual-frequency coil in a cold state and 1.0 x Us |
Safe isolation | 440 V AC, Between the contacts, According to EN 61140 440 V AC, Between coil and contacts, According to EN 61140 |
Power consumption, pick-up, 60 Hz | 62 VA, Dual-frequency coil in a cold state and 1.0 x Us 58 VA, Dual-frequency coil in a cold state and 1.0 x Us |
Screw size | M5, Terminal screw, Main cables M3.5, Terminal screw, Control circuit cables |
Power consumption, sealing, 50 Hz | 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us |
Power consumption, sealing, 60 Hz | 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us 6.5 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz 9.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
Terminal capacity (stranded) | 1 x 16 mm², Main cables |
Switching capacity (auxiliary contacts, general use) | 10 A, 600 V AC, (UL/CSA) 1 A, 250 V DC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA) A600, AC operated (UL/CSA) |
Terminal capacity (flexible with ferrule) | 2 x (0.75 – 10) mm², Main cables 2 x (0.75 – 2.5) mm², Control circuit cables 1 x (0.75 – 16) mm², Main cables 1 x (0.75 – 2.5) mm², Control circuit cables |
Resistenza agli urti | 5.3 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 6.9 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 3.5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Terminal capacity (solid) | 2 x (0.75 – 10) mm², Main cables 1 x (0.75 – 16) mm², Main cables 1 x (0.75 – 4) mm², Control circuit cables 2 x (0.75 – 2.5) mm², Control circuit cables |
Terminal capacity (solid/stranded AWG) | 18 – 14, Control circuit cables Single 18 – 6, double 18 – 8, Main cables |
Switching capacity (main contacts, general use) | 40 A, Maximum motor rating (UL/CSA) |
Power consumption | 7.5 kW |
Coppia di serraggio | 3.2 Nm, Screw terminals, Main cables 1.2 Nm, Screw terminals, Control circuit cables |
Rated control supply voltage (Us) at DC – max | 0 V |
Rated control supply voltage (Us) at DC – min | 0 V |
Tensione nominale di isolamento (Ui) | 690 V |
Rated making capacity up to 690 V (cos phi to IEC/EN 60947) | 238 A |
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V | 40 A |
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V | 18 A |
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 18 A |
Rated operational current (Ie) at AC-3, 440 V | 18 A |
Rated operational current (Ie) at AC-3, 500 V | 18 A |
Rated operational current (Ie) at AC-3, 660 V, 690 V | 12 A |
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V | 10 A |
Rated operational current (Ie) at AC-4, 400 V | 10 A |
Rated operational current (Ie) at AC-4, 440 V | 10 A |
Rated operational current (Ie) at AC-4, 500 V | 10 A |
Rated operational current (Ie) at AC-4, 660 V, 690 V | 8 A |
Rated operational current (Ie) at DC-1, 110 V | 35 A |
Rated operational current (Ie) at DC-1, 220 V | 35 A |
Rated operational current (Ie) at DC-1, 60 V | 35 A |
Corrente nominale di funzionamento per una dissipazione di calore specificata (In) | 18 A |
Rated operational power at AC-3, 240 V, 50 Hz | 5.5 kW |
Rated operational power at AC-3, 380/400 V, 50 Hz | 7.5 kW |
Rated operational power at AC-3, 415 V, 50 Hz | 10 kW |
Rated operational power at AC-4, 220/230 V, 50 Hz | 2.5 kW |
Rated operational power at AC-4, 240 V, 50 Hz | 3 kW |
Rated operational power at AC-4, 380/400 V, 50 Hz | 4.5 kW |
Rated operational power at AC-4, 415 V, 50 Hz | 5 kW |
Rated operational power at AC-4, 440 V, 50 Hz | 5.5 kW |
Rated operational power at AC-4, 500 V, 50 Hz | 6 kW |
Rated operational power at AC-4, 660/690 V, 50 Hz | 6.5 kW |
Rated operational power (NEMA) | 7.4 kW |
Rated operational voltage (Ue) at AC – max | 690 V |
Resistance per pole | 2.7 mΩ |
Static heat dissipation, non-current-dependent Pvs | 2.1 W |
Stripping length (control circuit cable) | 10 mm |
Stripping length (main cable) | 10 mm |
Switching time (AC operated, make contacts, closing delay) – max | 22 ms |
Switching time (AC operated, make contacts, closing delay) – min | 16 ms |
Switching time (AC operated, make contacts, opening delay) – max | 14 ms |
Switching time (AC operated, make contacts, opening delay) – min | 8 ms |
Short-circuit current rating (basic rating) | 125 A, max. CB, SCCR (UL/CSA) 5 kA, SCCR (UL/CSA) 125 A, max. Fuse, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 480 V) | 125/70 A, Class J, max. Fuse, SCCR (UL/CSA) 50/32 A, max. CB, SCCR (UL/CSA) 10/65 kA, CB, SCCR (UL/CSA) 10/100 kA, Fuse, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 600 V) | 10/100 kA, Fuse, SCCR (UL/CSA) 125/70 A, Class J, max. Fuse, SCCR (UL/CSA) 50/32 A, max. CB, SCCR (UL/CSA) 10/22 kA, CB, SCCR (UL/CSA) |
Short-circuit protection rating (type 1 coordination) at 400 V | 63 A gG/gL |
Suitable for | Also motors with efficiency class IE3 |
Short-circuit protection rating (type 1 coordination) at 690 V | 50 A gG/gL |
Short-circuit protection rating (type 2 coordination) at 400 V | 35 A gG/gL |
Short-circuit protection rating (type 2 coordination) at 690 V | 35 A gG/gL |
Special purpose rating of ballast electrical discharge lamps | 40 A (600V 60Hz 3phase, 347V 60Hz 1phase) 40 A (480V 60Hz 3phase, 277V 60Hz 1phase) |
Special purpose rating of definite purpose rating | 108 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 18 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) |
Special purpose rating of elevator control | 11 A, 480 V 60 Hz 3-ph, (UL/CSA) 11 A, 600 V 60 Hz 3-ph, (UL/CSA) 11 A, 200 V 60 Hz 3-ph, (UL/CSA) 3 HP, 200 V 60 Hz 3-ph, (UL/CSA) 9.6 A, 240 V 60 Hz 3-ph, (UL/CSA) 3 HP, 240 V 60 Hz 3-ph, (UL/CSA) 7.5 HP, 480 V 60 Hz 3-ph, (UL/CSA) 10 HP, 600 V 60 Hz 3-ph, (UL/CSA) |
Special purpose rating of refrigeration control (CSA only) | 180 A, LRA 600 V 60 Hz 3phase; (CSA) 40 A, FLA 480 V 60 Hz 3phase; (CSA) 30 A, FLA 600 V 60 Hz 3phase; (CSA) 240 A, LRA 480 V 60 Hz 3phase; (CSA) |
Special purpose rating of resistance air heating | 40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA) 40 A, 600 V 60 Hz 3p |
Peso | 1 kg |
---|---|
Dimensioni | 30 × 15 × 15 cm |
Devi effettuare l’accesso per pubblicare una recensione.


1. Elaborazione dell'ordine: Gli ordini vengono elaborati entro 1-2 giorni lavorativi dalla conferma del pagamento. I fine settimana e i giorni festivi sono esclusi dai tempi di elaborazione.
2. Opzioni e tempi di spedizione :
a.Spedizione standard: 3-7 giorni lavorativi (varia a seconda della destinazione).
b.Spedizione rapida: 2-3 giorni lavorativi (si applicano costi aggiuntivi).
c.Spedizione internazionale: 7-15 giorni lavorativi (la dogana può influire sulla consegna).
Note:
Per gli articoli in stock, spediamo entro 5 giorni lavorativi dalla ricezione del pagamento.
I prodotti esauriti o personalizzati saranno confermati via e-mail dopo l'invio dell'ordine.
3. Tracciabilità dell'ordine: Riceverete un numero di tracking via e-mail una volta spedito l'ordine. Utilizzate il nostro portale sullo stato dell'ordine per controllare gli aggiornamenti in tempo reale.
4. Problemi di consegna?
Consegne non riuscite: Contattate prima il vostro corriere locale e poi contattateci.
Articoli sbagliati o mancanti? Inviateci un'e-mail entro 7 giorni dalla consegna con i dettagli dell'ordine.
5. Note importanti Dogana e dazi: Gli acquirenti internazionali sono responsabili di eventuali tasse di importazione.
Accuratezza dell'indirizzo: Ricontrollare i dettagli della spedizione: non possiamo modificare gli ordini una volta elaborati!
Domande? Visitate il nostro Domande frequenti o contattare: support@isscasolutions.com
Recensioni
Ancora non ci sono recensioni.